What Are Cooling Classes?
Transformer cooling class designations describe how heat is removed from the transformer during operation. The cooling method directly affects the transformer's capacity rating and determines where it can be installed.
Reading Cooling Class Codes
Cooling class codes use four letters (or two pairs of two letters). The letter codes and what each position means are defined by IEC 60076-2, the standard governing temperature rise and cooling designations for oil-immersed transformers.
Position 1-2: Internal cooling medium and circulation Position 3-4: External cooling medium and circulation
Letter Meanings
| Letter | Position 1 | Position 2 | Position 3 | Position 4 |
|---|---|---|---|---|
| O | Mineral oil or synthetic insulating liquid with fire point at or below 300°C | - | - | - |
| K | Insulating liquid with fire point above 300°C (for example natural ester) | - | - | - |
| L | Insulating liquid with no measurable fire point | - | - | - |
| N | - | Natural convection | - | Natural convection |
| F | - | Forced circulation | - | Forced (fans or pumps) |
| D | - | Forced, directed through the windings | - | - |
| A | - | - | Air | - |
| W | - | - | Water | - |
Common Cooling Classes
ONAN (Oil Natural Air Natural)
The most common cooling class for distribution transformers.
How it works: Oil circulates naturally by convection; air flows naturally over radiators
Typical application: Distribution transformers up to ~10 MVA
Advantages: Simple, reliable, no auxiliary power needed
Limitations: Limited capacity; requires adequate ambient airflow
ONAF (Oil Natural Air Forced)
Adds fans to increase capacity.
How it works: Oil circulates naturally; fans force air over radiators
Typical application: Distribution and small power transformers, 2.5-30 MVA
Advantages: Higher capacity from same tank; fans only run when needed
Limitations: Requires auxiliary power; fan maintenance
Dual Rating: ONAN/ONAF transformers have two ratings:
ONAN rating (fans off): 75-80% of ONAF rating
ONAF rating (fans on): Full rating
A 10/12.5 MVA ONAN/ONAF transformer carries 10 MVA on natural convection alone and 12.5 MVA with the fans running, a 25 percent increase over the ONAN base rating. A 12/16/20 MVA ONAN/ONAF/ONAF transformer is a three-stage unit rather than a dual rating, with a three-rating nameplate and two stages of fans: 12 MVA ONAN base, 16 MVA on the first fan stage, and 20 MVA on the second. That 12/16/20 nameplate follows the 100/133/167 rating progression defined in IEEE C57.12.00.
As a general rule, a single stage of fans commonly adds 25 to 33 percent capacity over the ONAN base rating. The 25 percent figure is common practice for single-stage units rather than a value fixed by any standard.
OFAF (Oil Forced Air Forced)
Both oil and air are pumped for maximum cooling.
How it works: Pumps circulate oil; fans force air over radiators
Typical application: Large power transformers, 30+ MVA
Advantages: Maximum heat removal; highest power density
Limitations: Depends on pumps and fans; higher maintenance
ODAF (Oil Directed Air Forced)
Oil is directed through windings for targeted cooling.
How it works: Oil pumped through specific paths in windings; fans cool radiators
Typical application: Large power transformers, especially generator step-ups
Advantages: Most effective winding cooling; highest capacity
Limitations: Complex design; pump/fan dependent
OFWF (Oil Forced Water Forced)
Water cooling for special applications.
How it works: Oil pumped through oil-to-water heat exchangers
Typical application: Underground substations, industrial plants with cooling water
Advantages: Compact; no air heat rejection needed
Limitations: Requires cooling water supply; heat exchanger maintenance
What does ONAN mean?
ONAN (Oil Natural Air Natural) means the transformer is cooled entirely by convection: heat moves into the oil, the oil rises and circulates through the radiators on its own, and ambient air carries the heat away with no pumps or fans. ONAN units are the default for distribution transformers and for outdoor pad-mounted and pole-mounted installations, where no auxiliary power is available for fans. They are also common on lightly loaded substation transformers that never need the extra capacity forced cooling would provide.
What is the difference between ONAF and ODAF?
In an ONAF transformer, the oil circulates by natural convection and fans force air over the radiators. In an ODAF transformer, pumps circulate the oil and that oil is directed through the windings by ducts, so the flow is aimed at the hottest parts of the winding rather than left to find its own path. OFAF sits between the two: pumps circulate the oil through the radiators, but inside the windings the oil still moves by convection rather than being directed.
Dry-Type Cooling Classes
AN (Air Natural)
Self-cooled by natural convection
Most common for dry-type transformers
Typical up to ~5 MVA
AF (Air Forced)
Fans assist cooling
Higher ratings than AN
Common for larger dry-type units
ANV and GA
Non-ventilated (ANV) and sealed gas-filled (GA) dry-type designs enclose the core and coils for dirty, wet, or hazardous environments.
Selecting the Right Cooling Class
For Distribution Transformers (< 10 MVA)
ONAN is the default choice unless:
Space is very limited → Consider ONAF for more capacity per footprint
Indoor installation → Consider dry-type AN or AF
High ambient temperature → Consider ONAF for derating margin
For Power Transformers (10-100 MVA)
ONAN/ONAF dual-rated, or ONAN/ONAF/ONAF triple-rated above about 12 MVA, is typical for:
Normal utility and industrial applications
Moderate load cycling
Adequate installation space
OFAF is preferred when:
Maximum capacity from given footprint
Continuous high loading
Hot ambient conditions
For Large Power Transformers (100+ MVA)
ODAF or OFAF are standard due to:
High heat density in large windings
Need for reliable forced cooling
Often redundant cooling systems specified
Temperature Rise and Cooling
Transformer ratings assume specific temperature rise limits:
| Cooling Class | Typical Winding Rise | Typical Top Oil Rise |
|---|---|---|
| ONAN | 65°C | 65°C |
| ONAF | 65°C | 65°C |
| OFAF | 65°C | 65°C |
Temperature rise limits for oil-immersed transformers are set by IEEE C57.12.00: 65°C average winding rise, 65°C top oil rise, and 80°C hottest-spot rise over ambient. IEC 60076-2 uses slightly different limits, including a 60 K top oil rise.
65°C rise: the current IEEE standard, balancing capacity and insulation life.
55/65°C dual rise: an older convention still specified by some utilities. The unit is rated at 55°C rise and can carry about 12 percent more load at 65°C rise.
Altitude and Ambient Derating
Standard ratings assume:
1,000 meters altitude
30°C average ambient, 40°C maximum
Higher altitude or temperature requires derating or specifying enhanced cooling.